Simple room heat loss calculator
Estimate how much heat one room loses, in watts, at temperatures you choose: through its walls, windows and other surfaces, and through air leaving the room. You supply every area and U-value — nothing about your walls is guessed. This is a simplified steady-state worksheet for understanding heat flow, not a heater size or a building-code check.
Worked example (the pre-filled numbers)
Example assumptions only — the areas, U-values and air-change rate below are illustrative entries, not facts or defaults for any material or home. Inside 20 °C, outside 0 °C, so ΔT = 20 K. Walls: 100 m² × U 0.3 × 20 = 600 W. Windows: 10 m² × U 1.4 × 20 = 280 W. Through surfaces: 880 W. Air: 0.33 × 0.5 ACH × 200 m³ × 20 = 660 W. Total: about 1,540 W.
Method
Through each surface, heat flow in watts is U × net area × temperature difference, summed over all surfaces. Through air exchange it is approximately 0.33 × ACH × room volume in m³ × temperature difference. The 0.33 is a rounded constant, not an exact value: air's volumetric heat capacity is about 1,200 J/m³K, and 1,200 ÷ 3,600 s/h ≈ 0.333…, which this worksheet further rounds to 0.33. Areas in ft² are converted to m² and volumes in ft³ to m³ before use (1 ft = 0.3048 m exactly). Fahrenheit temperatures are converted to Celsius first, so a 36 °F difference correctly becomes a 20 K difference. If inside is not warmer than outside, the worksheet reports no heating heat loss rather than a negative number.
Your U-values must be in W/m²K for this page. If your figures are given as R-values or in imperial units, use the insulation U-value and R-value converter. This page offers no material menu, because a U-value belongs to a specific construction, not to a material name.
Limitations
Real rooms are not steady-state boxes. This worksheet ignores solar gains through glazing, heat from people and appliances, thermal bridging at junctions, wind-driven changes in leakage, moisture, thermal mass, and heat flow to neighbouring rooms at different temperatures; it also treats your ACH as constant. Results are only as good as the areas, U-values and ACH you enter, and are stated to the nearest watt for readability, not because the model is that precise. The total describes heat flow at the temperatures you chose: it does not recommend a heater or heat-pump size, and it is not a building-code or energy-rating assessment. For sizing or compliance, a qualified heating designer using the relevant national method is the right route.
Sources
Framework of fabric heat loss via element areas and U-values, as used in official dwelling energy methods: UK government, Standard Assessment Procedure (SAP) overview and Approved Document L (England; cited for the U×A framework only — no requirement values are used here, and other countries use their own methods). Unit conversions and the exact foot: NIST Guide to the SI, Appendix B.8. SI temperature and watt definitions: BIPM. The 0.33 air coefficient is a rounded engineering approximation (≈0.333… from about 1,200 ÷ 3,600, rounded to 0.33), not an exact constant; treat it as approximate.