Dew point and condensation calculator

Enter the room air temperature and relative humidity from a thermometer-hygrometer. This worksheet estimates the dew point: the temperature at which that air would begin to condense on a colder surface. Add a measured surface temperature, such as the coldest spot on a wall or window, to see whether it sits above or below that point on your readings.

1 · Indoor air
2 · Cold surface (optional)

Worked example

Air at 20 °C and 50% relative humidity, using the Magnus approximation below: ln(50 ÷ 100) = −0.6931, and 17.625 × 20 ÷ (243.04 + 20) = 1.3401, so γ = 0.6470. The dew point is 243.04 × 0.6470 ÷ (17.625 − 0.6470) ≈ 9.3 °C (48.7 °F). A surface measured at 8 °C is about 1.3 °C degrees below that point, so on those readings condensation is possible on it. At 100% humidity the dew point equals the air temperature.

Method

The dew point is estimated with the Magnus approximation for saturation vapour pressure over liquid water, with constants a = 17.625 and b = 243.04 °C: γ = ln(RH ÷ 100) + aT ÷ (b + T), then dew point Td = bγ ÷ (a − γ), with T in °C. Fahrenheit readings are converted to Celsius first ((°F − 32) × 5 ÷ 9), and results are shown in both scales. Where a surface temperature is given, the margin shown is surface temperature minus dew point; a surface at or below the dew point is reported as “condensation possible”, nothing stronger.

Limits

  • This is an approximation for indoor air between 0 °C and 50 °C over liquid water. It does not calculate a frost point, and a result below 0 °C should be read with that in mind.
  • “Condensation possible” describes only the two readings entered. Air movement, surface material, how long conditions last, and sensor error all affect what actually happens; allow a margin when a surface is close to the dew point.
  • This page does not diagnose mould, assess health, or set a target humidity or heating level for your home. Persistent condensation or mould needs the underlying cause checked in the building itself.
  • Readings vary around a room: air near a cold window is cooler and relatively more humid than air at a sensor across the room.

Sources

Last reviewed 16 November 2026. Calculations stay local: they happen in your browser, and nothing you enter is sent or stored.